Specifications |
LZZBJ9-10C1 current transformer |
Price Term: |
FOB |
Port of loading: |
SHEN ZHEN |
Minimum Order |
100 |
Unit Price: |
110 |
|
epoxy resin casting insulation and fully enclosed support construction, encloses the primary & secondary windings and annular core in the epoxy resin casting body. The product has the feature of light weight, omnidirectional installation, withstanding nastiness and dampness. It is widely used for measuring the current, electric energy and relay protection in the electrical system with the rated frequency 50Hz and rated voltage 10 kV or 11kV. Usage terms 1. Ambient temperature: -5-40° 2. Height above sea level within 1000m 3. Installation site: indoor Main technical parameter 1. Rated voltage: 10kV or 11kV 2. Rated secondary current: 5A or 1A 3. Highest voltage for equipment: 12 kV 4. Rated power-frequency withstand voltage: 42kV (GB standard ) or 28kV(IEC standard ) 5. Rated lightning impulse withstand voltage:75kV 6. Rated insulation level: 12/42/75kV (GB standard ) or 12/28/75 kV(IEC standard ) 7. Burden power factor: cos¢=0.8(lagging) 8. Standards: Current transformer:IEC60044-1.2003
|
Company: |
Jiu Jiang Yong Xin Can Equipment Co.,Ltd
|
Contact: |
Ms. WU Ying |
Address: |
No.005,antai road,automobile industry development zone jiu jiang city jiang xi province china |
Postcode: |
332007 |
Tel: |
86 792 8326977 |
Fax: |
86 792 8326978 |
E-mail: |
|
|
|
|